Comparison of transient overvoltage suppression capability of grid-forming converter and synchronous condenser

ZHANG Xing;LI Xu;TIAN Jie;WANG Jianan;DING Yong;LU Yu;

Abstract:

When faults such as blocking and commutation failure occur in a high-voltage direct current(HVDC) transmission system, they can cause transient voltage fluctuations near the sending-side converter station and lead to the disconnection with power grid. Firstly, the operating principles, response characteristics, and key parameter influences of the grid-forming energy storage open-loop control strategy are analyzed. Then, the reactive response characteristics of the synchronous condenser are analyzed, and a comparison is made between the grid-forming energy storage reactive power control model and the excitation regulation control model. Finally, a semi-physical simulation system is established, including EHVDC, photovoltaics, synchronous condenser, and grid-forming energy storage, to conduct comparative experiments on the effect of suppressing AC transient overvoltage under DC commutation failure. The results indicate that grid-forming energy storage and distributed synchronous condenser with the same capacity can achieve similar effects in terms of reactive transient response speed and the ability to suppress AC transient overvoltage.

Key Words: grid-forming energy storage;synchronous condenser;HVDC transmission system;commutation failure;reactive power support;transient overvoltage

Abstract:

Keywords:

Foundation: 国家重点研发计划(2022YFB2404905)

Authors: ZHANG Xing;LI Xu;TIAN Jie;WANG Jianan;DING Yong;LU Yu;

DOI: 10.19585/j.zjdl.202402010

References:

Accessibility
Information
Service
Key Words
The author of this article
Cnki
Share